Category 1 · Statutory inspections

    Local Exhaust Ventilation (LEV) & workplace ventilation

    COSHH reg. 9 requires that engineering controls provided to control exposure to hazardous substances — typically LEV systems — are examined and tested at suitable intervals. HSG258 sets out the industry-standard methodology for LEV thorough examination and test.

    Legal basis : COSHH 2002 reg. 9 · HSG258 · HSG202 (general ventilation) · CIBSE TM26

    Detailed inspection obligations

    Object of inspectionTypeFrequencyWhoRecordReference
    Thorough examination and test of LEV plantExamination + performance testEvery 14 months (COSHH default); more frequently for high-risk processes (e.g. metalworking fluids)Competent person (typically BOHS P601 qualified)LEV TExT report + logbook, held for 5 years minimumCOSHH 2002 reg. 9 · HSG258
    Weekly / monthly operator visual checksVisual and functional checkWeekly or as per commissioning reportTrained operatorLEV logbook entryHSG258 §4

    Object of inspectionTypeFrequencyWhoRecordReference
    Mechanical ventilation cleaning, filters and airflow ratesInspection and cleanPer BS EN 15780 / TR/19 categories (typically 12 months)Competent personVentilation hygiene recordWorkplace (H&S&W) Regulations 1992 reg. 6 · BS EN 15780

    Source. Content synthesised from HSE guidance and the source publication Statutory thorough examinations — UK duty holder overview (HSE ACoPs & BS EN standards, Updated 2026) This page is no substitute for the regulations in force or for a competent person's inspection report.